2.1 Start of the program
During the execution of the program it is possible to modify manually the flow rate or even stop the flow rate with ON/OFF button. However, the program will go further when the next step is executed. This allows performing certain emergency manipulations without terminating the program.
The running program can be terminated definitively by pressing the RUN button. The corresponding LED will go out.
After the last step of the program the gas flow will be stopped.
The maximum time period, which can be programmed in one step, is 255 min. If the time period is set to 000, then the step time is not limited and the flow rate will continue until the instrument is switched off.
| If you wish to maintain a certain flow rate at the end of the program, set the duration of the last step to 000. Such time is not defined and the flow rate will be maintained until the MASSFLOW is switched off manually or the power supply is disconnected. |
2.2 Reading the program
Reading the program is the same as the programming described above. No modification is made by the buttons under the display.
After the last step a simultaneous pressing of the REMOTE and RUN buttons will end the reading process. The message “END” will appear on the display. Pressing the RUN button will start the program.